Economies d'énergie grâce à l'amplification de la pression du liquide dans les systèmes frigorifiques.

Energy savings through liquid pressure amplification in refrigeration systems.

Résumé

Liquid pressure amplification (LPA) technology utilises a refrigerant pump in the liquid line after the receiver to maintain a high enough pressure differential across the expansion valve to compensate for the pressure drop in long liquid lines. This allows the condenser pressure to be varied in line with variations in ambient temperature leading to lower discharge pressures, during periods of low ambient temperatures, and lower compressor power consumption. This paper considers the application of LPA to a vapour compression refrigeration system for a chilled cold store in a dairy plant. The analysis has shown that the use of LPA in conjunction with liquid injection can lead to in excess of 10% energy savings over and above the savings that can be achieved with floating head pressure control alone.

Documents disponibles

Format PDF

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Energy savings through liquid pressure amplification in refrigeration systems.
  • Identifiant de la fiche : 2011-0124
  • Langues : Anglais
  • Source : IIR/Eurotherm sustainable refrigeration and heat pump technology conference. Proceedings of the Eurotherm Seminar No. 88, Stockholm, Sweden, June 13-16, 2010.
  • Date d'édition : 13/06/2010