Document IIF

Efficacité énergétique et sélection des cycles frigorifiques fonctionnant à l'ammoniac pour les entrepôts frigorifiques.

Energy efficiency and selection of ammonia refrigeration cycles in refrigerated warehouses.

Auteurs : ZHANG J., GROLL E. A.

Résumé

With the support of the International Association of Refrigerated Warehouses (IARW), a survey of the energy efficiencies of public refrigerated warehouses was conducted in the United States and Canada. Based on the results of this survey, the current use of ammonia as a refrigerant in warehouse applications by the IARW members is addressed in the paper. The relationships between energy efficiency and compression stages of the ammonia plants are discussed. Also, the difference in energy efficiency when using different types of intercoolers in two-stage ammonia compression plants is analysed. The results show that cycles with flash-type intercoolers are available and have higher efficiency. These should be adopted for new installations.

Documents disponibles

Format PDF

Pages : 2002-5

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Energy efficiency and selection of ammonia refrigeration cycles in refrigerated warehouses.
  • Identifiant de la fiche : 2003-2490
  • Langues : Anglais
  • Date d'édition : 17/09/2002
  • Source : Source : Proc. 5th IIR-Gustav Lorentzen Conf. nat. Working Fluids, Guangzhou/ C. R. Conf. Guangzhou, IIF
    2002-5; sess. 4; pap. 58; 454-458; fig.; tabl.; 3 ref.