Etude de la performance d'une pompe à chaleur de chauffage d'eau utilisant l'injection de liquide dans le système d'aspiration.

Study on performance of a heat pump water heater using suction stream liquid injection.

Auteurs : CAO F., FEI J., XING Z., et al.

Type d'article : Article

Résumé

Liquid refrigerant injection into a suction line is an effective and practical method to reduce the discharge temperature when a scroll compressor operates at high compression ratios. In the present study, correlations among the compressor suction temperature, discharge temperature, heat pump heating capacity, power consumption, COP and the quantity of suction liquid injection are established. The paper presents experimental analysis and a comparison with calculated results of the heat pump water heater (HPWH) performance with suction liquid injection in different conditions. It is found that the suction liquid injection explicitly lowers the discharge temperature of the compressor and the heating capacity of the unit, but the power consumption increases with COP decreasing. In addition, the highest injection ratio must be controlled fewer than 5%. The suction liquid injection has a better effect on the HPWH at the temperature ranging from -15 to 20°C. Within this temperature range, the 5% ratio suction liquid injection decreases the discharge temperature of the compressor by 10°C, while the heating capacity of the HPWH decreases by less than 5%, power consumption increases by less than 1.5%, and COP decreases by less than 7%. [Reprinted with permission from Elsevier. Copyright, 2009].

Détails

  • Titre original : Study on performance of a heat pump water heater using suction stream liquid injection.
  • Identifiant de la fiche : 2009-2020
  • Langues : Anglais
  • Source : Applied Thermal Engineering - vol. 29 - n. 14-15
  • Date d'édition : 10/2009
  • DOI : http://dx.doi.org/10.1016/j.applthermaleng.2009.03.001

Liens


Voir d'autres articles du même numéro (5)
Voir la source