Document IIF

Étude expérimentale de l'impact d'une mauvaise distribution d'air sur la performance d'un condenseur à tube à ailettes.

Experimental study on the influence of the air maldistribution on the performance of a finned tube condenser.

Numéro : pap. n. 464

Auteurs : PISANO A., MARTÍNEZ-BALLESTER S., CORBERÁN J. M., et al.

Résumé

In this work, an experimental analysis of the effects of the non-uniform air distribution on the performance of a finned tube condenser is presented. By using a suitably designed device for producing artificially an irregular air distribution at the condenser inlet, the effects of two different velocity profiles have been analyzed. In order to isolate the effect of the air maldistribution, the experimental campaign has been carried out maintaining constant the refrigerant inlet conditions and the mean value of the air velocity (2.5 m/s). The analysis is furthermore supported by the visualization of the wall temperature profile along the condenser by means of thermography and temperature sensors. The results show how the thermal capacity undergoes only slight changes, while the condensation temperature increases depending on the area of the heat exchanger where the heat rejection is penalized by the air maldistribution.

Documents disponibles

Format PDF

Pages : 8 p.

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Experimental study on the influence of the air maldistribution on the performance of a finned tube condenser.
  • Identifiant de la fiche : 30015898
  • Langues : Anglais
  • Source : Proceedings of the 24th IIR International Congress of Refrigeration: Yokohama, Japan, August 16-22, 2015.
  • Date d'édition : 16/08/2015
  • DOI : http://dx.doi.org/10.18462/iir.icr.2015.0464

Liens


Voir d'autres communications du même compte rendu (657)
Voir le compte rendu de la conférence