Document IIF
Étude expérimentale de l’utilisation de compresseurs bi-étagés à puissance variable dans des systèmes frigorifiques commerciaux légers au dioxyde de carbone transcritique.
An experimental study on the use of variable capacity two-stage compressors in transcritical carbon dioxide light commercial refrigerating systems.
Auteurs : CARVALHO B.Y. K. de, MELO C., HORN-PEREIRA R.
Type d'article : Article, Article de la RIF
Résumé
This paper focuses on experimentally investigating different cycle architectures with two-stage variable capacity compressors for light commercial refrigeration CO 2 systems. A system with two-stage rotary compressor and intercooler was used as a baseline. Tests with an iHX showed the existence of a minimum stable/safe superheating. Proper superheating control ( > 3 K) with an iHX increases the COP by 12.9%, 16.0%, and 17.2% in the compressor frequencies of 45, 60 and 75 Hz, respectively. To prevent instability a capillary tube selected for the lowest frequency can be used, but it reduces performance by up to 15.5% at higher frequencies. A cycle with iHX, two-stage expansion and intermediate flash-gas bypass was also studied. This cycle provided an average increase in cooling capacity of 7.5%, and gains in COP of 15.5%, 18.4% and 18.1%, at 45, 60 and 75 Hz, respectively. Flash-gas bypass control showed little benefit to performance, but improved cooling capacity by up to 12.1% when compared to the cycle with an iHX.
Documents disponibles
Format PDF
Pages : 604-615
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : An experimental study on the use of variable capacity two-stage compressors in transcritical carbon dioxide light commercial refrigerating systems.
- Identifiant de la fiche : 30027026
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 106
- Date d'édition : 10/2019
- DOI : http://dx.doi.org/10.1016/j.ijrefrig.2019.03.026
Liens
Voir d'autres articles du même numéro (54)
Voir la source
Indexation
-
Experimental study and modelling of a two-stage...
- Auteurs : VEGA J., GENDEBIEN S., LEMORT V.
- Date : 2022
- Langues : Anglais
- Source : 2022 Purdue Conferences. 19th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche
-
Modelling and analysis of CO2 gas coolers for c...
- Auteurs : SANTOSA I. M. C., SUAMIR I., GE Y. T., et al.
- Date : 02/04/2013
- Langues : Anglais
- Source : 2nd IIR International Conference on Sustainability and the Cold Chain. Proceedings: Paris, France, April 2-4, 2013.
- Formats : PDF
Voir la fiche
-
Development of a R744 low side variable speed s...
- Auteurs : TANG Y. J., LIU Y. G.
- Date : 16/07/2012
- Langues : Anglais
- Source : 2012 Purdue Conferences. 21st International Compressor Engineering Conference at Purdue.
- Formats : PDF
Voir la fiche
-
Preliminary experimental investigation on a tra...
- Auteurs : GULLO P., KÆRN M. R., BIRKELUND M., KRIEZI E. E.
- Date : 07/12/2020
- Langues : Anglais
- Source : 14th IIR-Gustav Lorentzen Conference on Natural Refrigerants (GL2020). Proceedings. Kyoto, Japon, December 7-9th 2020.
- Formats : PDF
Voir la fiche
-
Monitoring of a commercial refrigeration CO2 sy...
- Auteurs : AZZOLIN M., CALABRESE L., DUGARIA S., et al.
- Date : 09/07/2018
- Langues : Anglais
- Source : 2018 Purdue Conferences. 17th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF