Document IIF
Étude expérimentale de l’utilisation de compresseurs bi-étagés à puissance variable dans des systèmes frigorifiques commerciaux légers au dioxyde de carbone transcritique.
An experimental study on the use of variable capacity two-stage compressors in transcritical carbon dioxide light commercial refrigerating systems.
Auteurs : CARVALHO B.Y. K. de, MELO C., HORN-PEREIRA R.
Type d'article : Article, Article de la RIF
Résumé
This paper focuses on experimentally investigating different cycle architectures with two-stage variable capacity compressors for light commercial refrigeration CO 2 systems. A system with two-stage rotary compressor and intercooler was used as a baseline. Tests with an iHX showed the existence of a minimum stable/safe superheating. Proper superheating control ( > 3 K) with an iHX increases the COP by 12.9%, 16.0%, and 17.2% in the compressor frequencies of 45, 60 and 75 Hz, respectively. To prevent instability a capillary tube selected for the lowest frequency can be used, but it reduces performance by up to 15.5% at higher frequencies. A cycle with iHX, two-stage expansion and intermediate flash-gas bypass was also studied. This cycle provided an average increase in cooling capacity of 7.5%, and gains in COP of 15.5%, 18.4% and 18.1%, at 45, 60 and 75 Hz, respectively. Flash-gas bypass control showed little benefit to performance, but improved cooling capacity by up to 12.1% when compared to the cycle with an iHX.
Documents disponibles
Format PDF
Pages : 604-615
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : An experimental study on the use of variable capacity two-stage compressors in transcritical carbon dioxide light commercial refrigerating systems.
- Identifiant de la fiche : 30027026
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 106
- Date d'édition : 10/2019
- DOI : http://dx.doi.org/10.1016/j.ijrefrig.2019.03.026
Liens
Voir d'autres articles du même numéro (54)
Voir la source
Indexation
-
A study on carbon dioxide cycle architectures f...
- Auteurs : MONTAGNER G. P., MELO C.
- Date : 06/2014
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 42
- Formats : PDF
Voir la fiche
-
Transcritical CO2 commercial refrige...
- Auteurs : CORTELLA G., D'AGARO P., COPPOLA M. A.
- Date : 03/2020
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 111
- Formats : PDF
Voir la fiche
-
Using CO2 in supermarket refrigeration.
- Auteurs : SAWALHA S.
- Date : 08/2005
- Langues : Anglais
- Source : ASHRAE Journal - vol. 47 - n. 8
Voir la fiche
-
Performance assessment of a two-stage CO2<...
- Auteurs : CITARELLA B., MASTRULLO R., MAURO A. W., SFRAGARA M., TAMMARO M.
- Date : 11/2021
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 131
- Formats : PDF
Voir la fiche
-
Feasibility of CO2 compressors for light commer...
- Auteurs : OLIVA A., PÉREZ-SEGARRA C. D., RIGOLA J., et al.
- Date : 05/2007
- Langues : Anglais
- Source : HVAC&R Research - vol. 13 - n. 3
Voir la fiche