Document IIF
Étude expérimentale de la performance et de l'impact environnemental planétaire d'un système frigorifique rénové avec des frigorigènes alternatifs.
Experimental investigation on the performance and global environmental impact of a refrigeration system retrofitted with alternative refrigerants.
Auteurs : ANTUNES A. H. P., BANDARRA FILHO E. P.
Type d'article : Article, Article de la RIF
Résumé
This paper presents an experimental investigation of the drop-in process for HCFC-22 in a 5-ton refrigeration system. The original refrigerant was replaced by alternative halogenated refrigerants such as HFC-438A, HFC-404A, HFC-410A and HFC-32, as well as hydrocarbons HC-290 and HC-1270. The experimental facility was composed basically of a semi-hermetic reciprocating compressor, tube in tube heat exchangers and an electronic expansion valve. The tests were performed by just replacing the refrigerant, without changing any components, typically as in a drop-in process. The main parameters were varied to verify the range and performance of each refrigerant and then compared to the HCFC-22. Results showed that the natural refrigerants presented the best coefficient of performance and that results for HFCs, excepting the HFC-32, remained below those of HCFC-22. Regarding the environmental impact, using the parameter TEWI, the best results were reached with hydrocarbons; meanwhile, the refrigerant HFC-404A presented the highest environmental impact.
Documents disponibles
Format PDF
Pages : 119-127
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Experimental investigation on the performance and global environmental impact of a refrigeration system retrofitted with alternative refrigerants.
- Identifiant de la fiche : 30018649
- Langues : Anglais
- Sujet : Environnement, Alternatives aux HFC
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 70
- Date d'édition : 10/2016
Liens
Voir d'autres articles du même numéro (25)
Voir la source
Indexation
-
Thèmes :
HCFC;
HFC;
Hydrocarbures;
Efficacité energétique, économie d'énergie - Mots-clés : TEWI; Système frigorifique; HCFC; Remplacement immediat; R22; Performance; Hydrocarbure; HFC; Experimentation; Environnement; Frigorigène
-
Experimental evaluation of HCFC-22 replacement ...
- Auteurs : LLOPIS R., CABELLO R., SÁNCHEZ D., et al.
- Date : 05/2011
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 31 - n.6-7
Voir la fiche
-
Experimental comparison of drop-in process of R...
- Auteurs : ANTUNES A. H. P., SOUZA L., MENDOZA O., et al.
- Date : 16/08/2015
- Langues : Anglais
- Source : Proceedings of the 24th IIR International Congress of Refrigeration: Yokohama, Japan, August 16-22, 2015.
- Formats : PDF
Voir la fiche
-
Refrigerante propano: una alternativa eficiente...
- Auteurs : RECUERDA HERNÁNDEZ R.
- Date : 06/2001
- Langues : Espagnol
- Source : Instalador - n. 376
Voir la fiche
-
Replacement of HCFC-22 refrigerant with a drop-...
- Auteurs : LLOPIS R., CABELLO R., SÁNCHEZ D., et al.
- Date : 22/02/2012
- Langues : Anglais
- Source : CYTEF 2012. VI Congreso Ibérico y IV Congreso Iberoamericano de Ciencias y Técnicas del Frío, Madrid, España, 22-24 de febrero, 2012.
- Formats : PDF
Voir la fiche
-
R22 drop-in, a success at the Building Research...
- Auteurs : BUTLER D.
- Date : 09/1994
- Langues : Anglais
Voir la fiche