Etude expérimentale du contrôle du givre en utilisant des champs électriques continus ou alternatifs sur une plaque horizontale inclinée vers le bas.

An experimental investigation on frost control using DC and AC electric fields on a horizontal, downward-facing plate.

Auteurs : TUDOR V., OHADI M. M., FRANCA F. H. R.

Type d'article : Article

Résumé

The effects of DC and AC electric fields on frost formation on a horizontal downward-facing flat plate was investigated in the present experimental study. Frost growth was influenced and controlled by electric fields generated by an insulated wire electrode. In order to quantify the effects of DC and AC electric fields on frost growth, both mass transfer and frost height were measured. Experiments were carried out in a test section where environmental conditions including air temperature, humidity, and flow rate were controlled. When an AC electric field (with frequency ranging from 135 to 1000 Hz) was applied at predefined time intervals, the frost mass reduction ranged from 12% to 36%, while the frost height reduction was between 22% and 33%. On the other hand, continuous application of high voltage and high frequency (above 100 Hz) electric fields was found to increase the mass of frost by as much as 44% while strongly reducing the frost height (up to 65%). An intermittent DC electric field showed interesting effects on frost formation, with a mass frost reduction of up to 10%.

Détails

  • Titre original : An experimental investigation on frost control using DC and AC electric fields on a horizontal, downward-facing plate.
  • Identifiant de la fiche : 2004-2173
  • Langues : Anglais
  • Source : HVAC&R Research - vol. 9 - n. 2
  • Date d'édition : 04/2003
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres articles du même numéro (7)
Voir la source