Etude expérimentale du remplacement immédiat avec du R407C, dans un conditionneur d'air muni d'un évaporateur à contre-courant.

Experimental study of an R407C drop-in test on an off-the-shelf air conditioner with a counter-crossflow evaporator.

Résumé

Laboratory tests were performed using a paralel-cross-flow (PCF) evaporator and a counter-cross-flow (CCF) evaporator. The CCF configuration is designed to take advantage of the temperature glide of R407C. Test results indicated that the cooling capacity was 8% higher and system COP about 3.8% higher for the CCF evaporator than for the PCF evaporator. The test results also showed that the latent load for CCF was 30.6% higher than for PCF. The far better dehumidification effect provided by the CCF evaporator design is desirable for areas where the latent load is high.

Détails

  • Titre original : Experimental study of an R407C drop-in test on an off-the-shelf air conditioner with a counter-crossflow evaporator.
  • Identifiant de la fiche : 1999-3803
  • Langues : Anglais
  • Source : ASHRAE Transactions. 1998 annual Meeting, Toronto, Ontario + CD-ROM.
  • Date d'édition : 1998