Document IIF

Étude expérimentale effectuée sur le transfert de chaleur des tubes à ailettes sous des conditions de givrage.

Experimental investigation on heat transfer of fin-tube under frost condition.

Numéro : pap. ID: 232

Auteurs : KWAK D. K., KIM S., CHO K., et al.

Résumé

The present study measured frost characteristics and heat transfer rate of scale-up fin-tube model, and predicted those of scale-down fin-tube prototype. The scale-up model has the tube diameter of 22 mm and fin size of 40 x 76 mm, while the scale-down prototype has the tube diameter of 7mm and the fin size of 12.6 x 28 mm. The test conditions were air temperature of 2°C , absolute humidity of 3.7 g/kgDA, air velocity from 0.5 to 1.5 m/s, and coolant temperature of -10°C. The coolant was ethylene-glycol aqueous solution with the concentration of 50%. Frost characteristics and heat transfer rates for the prototype were predicted by using data for the model and similarity principle. The predicted values were compared with the data measured for the prototype. They agreed within 10%.

Documents disponibles

Format PDF

Pages : 8 p.

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Experimental investigation on heat transfer of fin-tube under frost condition.
  • Identifiant de la fiche : 30002277
  • Langues : Anglais
  • Source : Proceedings of the 23rd IIR International Congress of Refrigeration: Prague, Czech Republic, August 21-26, 2011. Overarching theme: Refrigeration for Sustainable Development.
  • Date d'édition : 21/08/2011

Liens


Voir d'autres communications du même compte rendu (569)
Voir le compte rendu de la conférence