Étude expérimentale sur la performance d'un échangeur de chaleur à cascade au NH3/CO2.

[In Chinese. / En chinois.]

Auteurs : LIU C., WANG C.

Type d'article : Article

Résumé

As the promotion and the applicat ion of NH3/CO2 cascade refrigeration system, the development of efficient cascade heat exchanger becomes more and more important to improve the performance of the system. Based on the experimental study of a NH3/CO2 cascade refrigeration system, and the analysis of the effect caused by operating condition and the number of heat exchanger tubes on the temperature difference of heat transfer, heat flux and coefficient of heat transfer, we conclude that the heat transfer coefficient of NH3/CO2, cascade heat exchanger is within 1987~2378 W/(m2.K) in engineering design. The experimenl of the cascade heat exchanger is used to optimize the design of heat exchanger. which result in the decrease of heat transfer area by 60% and great reduction of manufacturing cost of cascade heat exchanger.

Documents disponibles

Format PDF

Pages : 72-78

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : [In Chinese. / En chinois.]
  • Identifiant de la fiche : 30003131
  • Langues : Chinois
  • Source : Journal of Refrigeration - n. 140
  • Date d'édition : 08/2011

Liens


Voir d'autres articles du même numéro (13)
Voir la source