Etude expérimentale sur la performance en termes de condensation d'un échangeur de chaleur à ailettes et tubes plats.

Experimental investigation on condensation performance of fin-and-flat-tube heat exchanger.

Auteurs : LIANG X., XING S., ZHUANG R., et al.

Résumé

Condensation heat transfer performance of a louvered fin-and-flat-tube heat exchanger (FTHX) in single slab and in residential air-conditioning system were experimentally investigated, and were compared with fin-and-circular-tube heat exchangers (CTHX) under the same testing conditions. The test results showed that: FTHX had the characteristics of low pressure drop of air side, high pressure drop of refrigerant side and less refrigerant charge; the overall heat transfer performance of copper FTHX was higher than that of diameter 7 mm CTHX but a little lower than that of diameter 9.52 mm CTHX; the cooling capacity and EER of the residential air-conditioning system with FTHX were a little lower than those of the system with diameter 9.52 mm CTHX.

Documents disponibles

Format PDF

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Experimental investigation on condensation performance of fin-and-flat-tube heat exchanger.
  • Identifiant de la fiche : 2010-1795
  • Langues : Anglais
  • Date d'édition : 12/07/2010
  • Source : Source : Proc. 2010 int. Refrig. Air Cond. Conf., Purdue Univ.
    n. 2150; 5 p.; fig.; photogr.; tabl.; 2 ref.