Document IIF

Étude expérimentale sur le R600a en ébullition à l'intérieur d'un tube d'un diamètre de 2,6 mm.

Experimental study of R600a boiling in 2.6 mm tube.

Numéro : pap. ID: 646

Auteurs : COPETTI J. B., MACAGNAN M. H., KUNSLER N. L. F., et al.

Résumé

Evaporators for small and medium refrigeration systems, designed using reduced diameter channels, are a main focus in the development of compact refrigeration equipments. Moreover, new refrigerants are currently being tested to substitute HFCs. Therefore, the objective of this work is to experimentally characterize heat transfer and pressure drop during boiling of isobutane (R600a) in a horizontal mini tube. The test section was 185 mm long and had 2.6 mm of internal diameter. Experimental conditions comprised heat fluxes of 44, 63 and 95 kW/m2, mass velocities of 240 and 440 kg/m2.s and saturation temperature of 22°C. The results were compared to previous ones using R134a. It was possible to observe the influence of heat flux and mass velocity on the heat transfer coefficient and on the frictional pressure drop. The R600a showed higher heat transfer coefficients and frictional pressure drop. This behaviour is related to distinct thermophysical properties among refrigerants.

Documents disponibles

Format PDF

Pages : 8 p.

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Experimental study of R600a boiling in 2.6 mm tube.
  • Identifiant de la fiche : 30002102
  • Langues : Anglais
  • Source : Proceedings of the 23rd IIR International Congress of Refrigeration: Prague, Czech Republic, August 21-26, 2011. Overarching theme: Refrigeration for Sustainable Development.
  • Date d'édition : 21/08/2011

Liens


Voir d'autres communications du même compte rendu (569)
Voir le compte rendu de la conférence