Document IIF

Étude expérimentale sur le séparateur dans le système frigorifique à détente par éjecteur.

Experimental study on the separator in ejector-expansion refrigeration system.

Auteurs : LIN C., XU C., BAO Y., et al.

Type d'article : Article, Article de la RIF

Résumé

In this study, an experimental platform was built to investigate the separation performance of 4 designed different separators which had significant influence on ejector-expansion system performance, by means of visualization and heat balance method. The results showed the oblique injection separator with top outlet pipe inserting inside the separation tank presented the best performance, reaching 244?W cooling capacity at -25?°C evaporation temperature. With such separator, the COP of ejector-expansion refrigeration system could be improved by 16.7% at -30?°C evaporation temperature compared with normal refrigeration system. However, as the evaporation temperature increased further, the ejector showed less significant impact on the system performance.

Documents disponibles

Format PDF

Pages : 307-314

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Experimental study on the separator in ejector-expansion refrigeration system.
  • Identifiant de la fiche : 30025638
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 100
  • Date d'édition : 04/2019
  • DOI : http://dx.doi.org/10.1016/j.ijrefrig.2019.02.015

Liens


Voir d'autres articles du même numéro (46)
Voir la source