Etude paramétrique de la performance d'un diffuseur dans un système d'accumulation d'eau glacée. 2. Analyse dimensionnelle, simulations paramétriques et développement d'un modèle simplifié.

Parametric study of charging inlet diffuser performance in stratified chilled water storage tanks with radial diffusers. 2. Dimensional analysis, parametric simulations and simplified model development.

Auteurs : MUSSER A., BAHNFLETH W. P.

Type d'article : Article

Résumé

Part 2 of this article summarizes the results of the parametric study (see also the Bulletin of the IIR, reference 2002-0978). Dimensional storage tank and inlet diffuser parameters having the potential to influence inlet thermal performance were identified, then formed into dimensionless groups. Thermal performance was measured in terms of thermocline thickness and equivalent lost tank height. Sixteen simulations comprising a full 2 to the power of factorial experiment were completed and analyzed.

Détails

  • Titre original : Parametric study of charging inlet diffuser performance in stratified chilled water storage tanks with radial diffusers. 2. Dimensional analysis, parametric simulations and simplified model development.
  • Identifiant de la fiche : 2002-1603
  • Langues : Anglais
  • Source : HVAC&R Research - vol. 7 - n. 2
  • Date d'édition : 04/2001
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.