Etude sur l'injection du frigorigène liquide dans un compresseur frigorifique semi-hermétique à piston.

[In Chinese. / En chinois.]

Auteurs : WANG F., GUO Q., LI L.

Type d'article : Article

Résumé

The experiment was conducted to explore the effect of liquid refrigerant injection on the performance of a semi-hermetic reciprocating refrigerating compressor and the variation of the liquid refrigerant injection ratio with evaporation temperature and condensation temperature on a Sanyo model under different conditions. The results show that the liquid refrigerant injection can effectively reduce the discharge temperature, but will increase the compressor power and reduce the refrigerating capacity and the COP. The injection ratio is non-linear with the discharge temperature. The optimization of the liquid refrigerant injection ratio by selecting the capillary tube for injection can ensure the compressor performance as well as the discharge temperature.

Documents disponibles

Format PDF

Pages : pp. 29-33

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails


Liens


Voir d'autres articles du même numéro (7)
Voir la source