Études expérimentales complètes de la performance d’un système au CO2 transcritique à détente par éjecteur.

Comprehensive experimental studies on performance of an ejector expansion transcritical CO2 system.

Numéro : pap. L21

Auteurs : ZHU Y., LI C., JIANG P. X.

Résumé

The ejector performance and cooling performances of ejector expansion CO2 cycle were investigated comprehensively. The mass flow rates and the entrainment ratio of the ejector were obtained based on accurate experiments at various primary flow pressures, secondary flow pressures and back pressures. The secondary mass flow rate increases with increasing primary flow and secondary flow pressure and decreases with increasing back pressure. Both COP and the entrainment ratio decrease as the back pressure increases. The pressure lift ratio is inversely proportional to the entrainment ratio, which means a large pressure lift resulting in a small entrainment ratio.

Documents disponibles

Format PDF

Pages : 9

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Comprehensive experimental studies on performance of an ejector expansion transcritical CO2 system.
  • Identifiant de la fiche : 30022046
  • Langues : Anglais
  • Source : 8th international conference on compressors and refrigeration, 2017.
  • Date d'édition : 20/07/2017

Liens


Voir d'autres communications du même compte rendu (97)
Voir le compte rendu de la conférence