Evaluation d'un refroidisseur à sorption fonctionnant à l'aide d'un système de cogénération dans un immeuble résidentiel.

Assessment of a sorption chiller driven by a cogeneration unit in a residential building.

Auteurs : KEGEL M., SUNYÉ R., GALANIS N., et al.

Résumé

This paper describes the TRNSYS model developed to investigate the techno-economic feasibility of a small-scale trigeneration system for residential or small business applications. A 210 m2 single family home located in Ontario and equipped with a commercially available 6 kWe micro cogeneration system where cooling is provided by a chiller relying on either absorption or adsorption principles was simulated. The results anticipated reductions of approximately 25-35% in primary energy consumption, 150% in GHG emissions and 60% in utility costs. However, it was found more work is needed to address the relatively high cost of sorption systems and low operating times.

Documents disponibles

Format PDF

Pages : 607-614

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Assessment of a sorption chiller driven by a cogeneration unit in a residential building.
  • Identifiant de la fiche : 30001258
  • Langues : Anglais
  • Source : Sources/sinks Alternative to the Outside Air for Heat Pump and Air-conditioning Techniques (Alternative Sources - AS), Padua, Italy, April 5-7, 2011. / International Sorption Heat Pump Conference (ISHPC11), Padua, Italy, April 6-8, 2011.
  • Date d'édition : 06/04/2011

Liens


Voir d'autres communications du même compte rendu (122)
Voir le compte rendu de la conférence