Document IIF

Evaluation de la composition de systèmes frigorifiques ou de pompes à chaleur utilisant des mélanges de frigorigènes zéotropiques.

Estimation of composition in refrigeration and heat-pump systems using zeotropic refrigerant mixtures.

Auteurs : LUNDQVIST P. G.

Résumé

The paper deals with issues related to performance evaluation of zeotropic alternatives such as R407C or Isceon 59. Refrigerant retrofits to alternative refrigerants are often evaluated experimentally in laboratories or under field-like conditions. But composition changes may alter these measurements. The paper addresses this problem for a number of possible causes to composition changes (leakage, refrigerant hold-up, selective solubility, etc.) The paper shows that it is possible to monitor selected parameters such as sub-cooling or superheat to detect changes in composition. The paper also shows that it is difficult to draw conclusions regarding composition changes from observations of the COP, or the cooling capacity.

Documents disponibles

Format PDF

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Estimation of composition in refrigeration and heat-pump systems using zeotropic refrigerant mixtures.
  • Identifiant de la fiche : 2000-1278
  • Langues : Anglais
  • Source : 20th International Congress of Refrigeration: Refrigeration into the Third Millennium.
  • Date d'édition : 19/09/1999

Liens


Voir d'autres communications du même compte rendu (447)
Voir le compte rendu de la conférence