Évaluation de la performance d'un bâtiment en gypse renforcé par des fibres de verre activées thermiquement et équipé d'un système à déshydratant.

Performance Evaluation of thermally activated glass fibre reinforced gypsum building equipped with desiccant system.

Numéro : pap. 3506

Auteurs : MURUGANANTHAM S., DHARMASASTHA K., GURUBALAN A., et al.

Résumé

A thermally activated glass fiber reinforced gypsum building (1m x 1m x 1m) equipped with desiccant system is proposed and investigated for the hot and humid climatic conditions. It effectively controls the temperature and humidity of the indoor, closer to comfort condition. In the present study, the influence of temperature and flow rate of the cooling water are experimentally investigated for the thermal performance on the proposed system. The performance indices are indoor temperature, relative humidity, operative temperature, PMV and PPD. It is found that even at 38 oC (OAT), 40% (R.H) ambient condition, the proposed system maintains the comfort environment with the inlet temperature and flow rate of the cooling water as 20oC and 350 lph respectively.

Documents disponibles

Format PDF

Pages : 7

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Performance Evaluation of thermally activated glass fibre reinforced gypsum building equipped with desiccant system.
  • Identifiant de la fiche : 30024896
  • Langues : Anglais
  • Source : 2018 Purdue Conferences. 5th International High Performance Buildings Conference at Purdue.
  • Date d'édition : 09/07/2018

Liens


Voir d'autres communications du même compte rendu (88)
Voir le compte rendu de la conférence