Document IIF
Évaluation de la performance d'un système frigorifique à injection de vapeur utilisant un mélange de frigorigènes R290/R600a.
Performance evaluation of a vapor injection refrigeration system using mixture refrigerant R290/R600a.
Auteurs : ANGELO J. V. H. d', AUTE V., RADERMACHER R.
Type d'article : Article, Article de la RIF
Résumé
This work presents a performance evaluation of a vapor injection refrigeration system using a mixture refrigerant R290/R600a, through steady-state simulations used to accomplish a parametric analysis considering the influence of the refrigerant composition over the following parameters: COP; compressor power; refrigerant mass flow rate; refrigerant temperature glide; mass flow ratio between vapor and feed streams in the flash tank; liquid and vapor composition of flash tank outlet streams and compression ratio. Two cases, denominated A and B, considering different fixed temperatures at the refrigeration system were studied and their performances were compared with the one of a basic vapor compression cycle. A maximum COP was obtained for a mixture containing 40 wt% of R290. COP of vapor injection refrigeration cycle is 16–32% greater than the one of a vapor compression cycle, depending on the composition of the mixture refrigerant and pressure drop at the cycle upper-stage expansion valve.
Documents disponibles
Format PDF
Pages : 194-208
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Performance evaluation of a vapor injection refrigeration system using mixture refrigerant R290/R600a.
- Identifiant de la fiche : 30017239
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 65
- Date d'édition : 05/2016
Liens
Voir d'autres articles du même numéro (25)
Voir la source
Indexation
-
Thèmes :
Hydrocarbures;
Mélanges;
Efficacité energétique, économie d'énergie - Mots-clés : Système frigorifique; R600a; Vapeur; R290; Performance; Mélange; Injection; Frigorigène
-
Energy performance evaluation of R1234yf, R1234...
- Auteurs : SÁNCHEZ D., CABELLO R., LLOPIS R., et al.
- Date : 02/2017
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 74
- Formats : PDF
Voir la fiche
-
Modeling of a novel spool compressor with multi...
- Auteurs : MATHISON M. M., BRAUN J. E., GROLL E. A.
- Date : 11/2013
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 36 - n. 7
- Formats : PDF
Voir la fiche
-
Energy comparison based on experimental results...
- Auteurs : CABELLO R., ANDREU-NACHER A., SÁNCHEZ D., LLOPIS R., VIDAN-FALOMIR F.
- Date : 04/2023
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 148
- Formats : PDF
Voir la fiche
-
Experimental investigation on the performance a...
- Auteurs : ANTUNES A. H. P., BANDARRA FILHO E. P.
- Date : 10/2016
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 70
- Formats : PDF
Voir la fiche
-
A propos de l'efficacité des mélanges de R125/R...
- Auteurs : VASSERMAN A. A., MALCHEVSKIJ V. P.
- Date : 09/2008
- Langues : Russe
- Source : Holodil'nyj Biznes - n. 9
- Formats : PDF
Voir la fiche