Document IIF

Évaluation de la performance d'un système frigorifique à injection de vapeur utilisant un mélange de frigorigènes R290/R600a.

Performance evaluation of a vapor injection refrigeration system using mixture refrigerant R290/R600a.

Auteurs : ANGELO J. V. H. d', AUTE V., RADERMACHER R.

Type d'article : Article, Article de la RIF

Résumé

This work presents a performance evaluation of a vapor injection refrigeration system using a mixture refrigerant R290/R600a, through steady-state simulations used to accomplish a parametric analysis considering the influence of the refrigerant composition over the following parameters: COP; compressor power; refrigerant mass flow rate; refrigerant temperature glide; mass flow ratio between vapor and feed streams in the flash tank; liquid and vapor composition of flash tank outlet streams and compression ratio. Two cases, denominated A and B, considering different fixed temperatures at the refrigeration system were studied and their performances were compared with the one of a basic vapor compression cycle. A maximum COP was obtained for a mixture containing 40 wt% of R290. COP of vapor injection refrigeration cycle is 16–32% greater than the one of a vapor compression cycle, depending on the composition of the mixture refrigerant and pressure drop at the cycle upper-stage expansion valve.

Documents disponibles

Format PDF

Pages : 194-208

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Performance evaluation of a vapor injection refrigeration system using mixture refrigerant R290/R600a.
  • Identifiant de la fiche : 30017239
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 65
  • Date d'édition : 05/2016

Liens


Voir d'autres articles du même numéro (25)
Voir la source