Évaluation de la performance de fonctionnement sans givre de pompes à chaleur hybrides déshydratantes.

Performance evaluation of frost-free operation of desiccant hybrid heat pumps.

Numéro : pap. n. 131

Auteurs : HIHARA E., KOYANO T., NAKAGAWA N., et al.

Résumé

This paper proposes a desiccant hybrid heat pump for enabling frost-free operation of heat pumps in humid regions in winter. Experimental measurements using mesoporous silica, which can operate at low temperatures, validated that removal of water vapor from the incoming air of the evaporator was effective in preventing the formation of frost. The results also confirmed that this system provides higher efficiency if the absorbed water can be used for humidification. Based on the experimental results, a theoretical model was constructed and results of a simulation using this model showed that the proposed system could meet the humidity requirement in a relatively wide range (0.5–1) of the sensible heat factor.

Documents disponibles

Format PDF

Pages : 10 p.

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Performance evaluation of frost-free operation of desiccant hybrid heat pumps.
  • Identifiant de la fiche : 30013654
  • Langues : Anglais
  • Source : International sorption heat pump conference (ISHPC2014), College Park, United States, March 31-April 2, 2014.