Évaluation des performances et analyse comparative des systèmes frigorifiques transcritiques à surpression de CO2 avec refroidisseur de gaz évaporatif modifié pour les supermarchés dans le contexte indien.

Performance evaluation and comparative analysis of trans-critical CO2 booster refrigeration systems with modified evaporative cooled gas cooler for supermarket application in Indian context.

Auteurs : LATA M., GUPTA D. K.

Type d'article : Article de la RIF

Résumé

In this paper, the performance of CO2 booster refrigeration systems with eight different configurations for the supermarket application is analysed and compared with the conventional R404A system. The investigated configurations includes basic booster system with overfeed evaporators, as well as the adoption of modified evaporative cooled gas cooler. The analysis is mainly focused on power consumption, energy efficiency, and total equivalent warming impact while using these systems throughout the year in Indian climatic conditions. The steady-state thermodynamic model is developed and validated for the booster systems available in the literature. Subsequently, the analysis is extended for all the configurations on the year-round operation (2017–18) for five major cities in India of different climate regions. The result shows that the basic booster system with both low and medium temperature flooded evaporators integrated with modified evaporative cooler system is the best configuration in all cities. The rank of performance is higher for Delhi (composite climate region), followed by Ahmedabad, Bangalore, Chennai, and Kolkata (hot and humid climate region). The BBSM-LT+MT system, improve the SEER maximum up to 49%, whereas the annual energy saving up to 35%, compared to the BBS. Subsequently, the maximum reduction in indirect emission (TEWI) is found to be 18% compared to the conventional R404A system.

Documents disponibles

Format PDF

Pages : 248-259

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Performance evaluation and comparative analysis of trans-critical CO2 booster refrigeration systems with modified evaporative cooled gas cooler for supermarket application in Indian context.
  • Identifiant de la fiche : 30027857
  • Langues : Anglais
  • Sujet : Technologie
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 120
  • Date d'édition : 12/2020
  • DOI : http://dx.doi.org/10.1016/j.ijrefrig.2020.08.004