Evaluation du dioxyde de carbone en tant que substitut du R22 dans le domaine du conditionnement d'air résidentiel.
Evaluation of carbon dioxide as R22 substitute for residential air conditioning.
Auteurs : BROWN J. S., KIM Y., DOMANSKI P. A.
Résumé
The R22 system had a significantly better coefficient of performance (COP) than the CO2 system when equivalent heat exchangers were used in the CO2 and R22 systems, which indicates that the better transport properties and compressor isentropic efficiency of CO2 did not compensate for the thermodynamic disadvantage of the transcritical cycle in comfort cooling applications. An entropy generation analysis showed that the CO2 evaporator operated with fewer irreversibilities than did the R22 evaporator. However, the CO2 gas cooler and expansion device generated more entropy than their R22 counterparts and were mainly responsible for the low COP of the CO2 system.
Détails
- Titre original : Evaluation of carbon dioxide as R22 substitute for residential air conditioning.
- Identifiant de la fiche : 2004-0358
- Langues : Anglais
- Source : ASHRAE Transactions. 2002 annual Meeting, Honolulu, Hawaii. Volume 108, part 2 + CD-ROM.
- Date d'édition : 2002
Liens
Voir d'autres communications du même compte rendu (85)
Voir le compte rendu de la conférence
Indexation
-
Thèmes :
Autres équipements de conditionnement d'air;
HCFC;
CO2 - Mots-clés : Application domestique; R22; Substitut; Experimentation; Frigorigène; Conditionnement d'air; CO2
-
Hydrocarbon refrigerant as an alternative refri...
- Auteurs : PASEK A. D., SUWONO A.
- Date : 01/08/2004
- Langues : Anglais
- Source : Natural Working Fluids 2004: 6th IIR-Gustav Lorentzen Conference
- Formats : PDF
Voir la fiche
-
Expérience sur le remplacement du R22 par le R2...
- Auteurs : LI T., YANG J., ZENG Z., et al.
- Date : 08/2010
- Langues : Chinois
- Source : Journal of Refrigeration - vol. 31 - n. 4
- Formats : PDF
Voir la fiche
-
L'Isceon 59 fait planer la Royal Air Force (RAF).
- Date : 02/1999
- Langues : Français
- Source : La revue pratique du froid et du conditionnement d'air - n. 865
Voir la fiche
-
A comparative evaluation of CO2 and HCFC-22 roo...
- Auteurs : PETTERSEN J., AARLIEN R., NEKSA P., SKAUGEN G., AFLEKT K.
- Date : 13/05/1997
- Langues : Anglais
- Source : CO2 Technology in Refrigeration, Heat Pump & Air Conditioning Systems. Workshop Proceedings.
- Formats : PDF
Voir la fiche
-
Expérience sur le THR03 : un frigorigène pour r...
- Auteurs : SHI L., HAN L., ZHU M., et al.
- Date : 04/2000
- Langues : Chinois
- Source : HV & AC - vol. 30 - n. 133
Voir la fiche