Expérience acquise de longue date avec un système d'accumulation thermique avec fonte de glace externe.
Long-term experience with external-melt ice-on-coil storage cooling system.
Auteurs : SOHN C. W., NIXON J. L.
Résumé
Yuma Proving Ground, Arizona, has successfully operated an external-melt ice-on-coil storage cooling system with nominal tank storage capacity of 1050 ton-h (3692 kWh) for the past 12 years. The ice storage system was a retrofitted "add-on" to the existing chilled water system and consists of one 220-ton (774 KW) centrifugal chiller and one 80-ton (281 KW) reciprocating chiller. The system's design objective was to eliminate the electrical demand of the 220-ton (774 KW) chiller during the peak window of 1200-1600 hours. Yearly net savings of $22,450 in electrical utility costs paid back the construction cost of $144 969 in 6.5 years.
Détails
- Titre original : Long-term experience with external-melt ice-on-coil storage cooling system.
- Identifiant de la fiche : 2002-0989
- Langues : Anglais
- Source : ASHRAE Transactions. 2001 Winter Meeting, Atlanta, GA. Volume 107, part 1 + CD-ROM.
- Date d'édition : 2001
- Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.