Expérience acquise de longue date avec un système d'accumulation thermique avec fonte de glace externe.
Long-term experience with external-melt ice-on-coil storage cooling system.
Auteurs : SOHN C. W., NIXON J. L.
Résumé
Yuma Proving Ground, Arizona, has successfully operated an external-melt ice-on-coil storage cooling system with nominal tank storage capacity of 1050 ton-h (3692 kWh) for the past 12 years. The ice storage system was a retrofitted "add-on" to the existing chilled water system and consists of one 220-ton (774 KW) centrifugal chiller and one 80-ton (281 KW) reciprocating chiller. The system's design objective was to eliminate the electrical demand of the 220-ton (774 KW) chiller during the peak window of 1200-1600 hours. Yearly net savings of $22,450 in electrical utility costs paid back the construction cost of $144 969 in 6.5 years.
Détails
- Titre original : Long-term experience with external-melt ice-on-coil storage cooling system.
- Identifiant de la fiche : 2002-0989
- Langues : Anglais
- Source : ASHRAE Transactions. 2001 Winter Meeting, Atlanta, GA. Volume 107, part 1 + CD-ROM.
- Date d'édition : 2001
- Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.
Liens
Voir d'autres communications du même compte rendu (60)
Voir le compte rendu de la conférence
Indexation
-
Discussion of water-accumulating-cooling air co...
- Auteurs : MA Z. K., CHENG T., LV G., ZHANG P.
- Date : 09/09/1997
- Langues : Anglais
- Source : International Symposium on Air Conditioning in High Rise Buildings - 1997
- Formats : PDF
Voir la fiche
-
Operating strategy for dynamic ice thermal stor...
- Auteurs : MOORE J. E., HARMON J. J.
- Date : 1998
- Langues : Anglais
- Source : ASHRAE Transactions. 1998 Winter Meeting, San Francisco, CA.
Voir la fiche
-
Operating characteristics of five stratified ch...
- Auteurs : STEWART W. E.
- Date : 24/06/2001
- Langues : Anglais
- Source : ASHRAE Transactions. 2001 annual Meeting, Cincinnati, Ohio. Volume 107, part 2 + CD-ROM.
Voir la fiche
-
Study on fault detection of thermal storage tan...
- Auteurs : ZHENG M., PAN S., NAKAHARA N.
- Date : 09/09/1997
- Langues : Anglais
- Source : International Symposium on Air Conditioning in High Rise Buildings - 1997
- Formats : PDF
Voir la fiche
-
Chilled water storage performance improvement.
- Auteurs : GANSLER R. A., REINDL D. T., TOMPKINS D. T.
- Date : 07/08/1996
- Langues : Anglais
- Source : EPRI International Conference on sustainable thermal energy storage (TES). Conference Proceedings.
Voir la fiche