Expérience sur la performance d'un système frigorifique au R-290/CO2 en cascade.

[In Chinese. / En chinois.]

Auteurs : NING J., LI H., PENG M.

Type d'article : Article

Résumé

Performance experiments of R-290/CO2 cascade refrigeration system were conducted. The performance of a cascade refrigeration system having a high temperature cycle using R-290 as refrigerant and a CO2 based low temperature cycle was compared with that of a cascade refrigeration system having a high temperature cycle using R-22 as refrigerant and a CO2 based low temperature cycle. The results show that the optimum mass flow ratio and the maximum COP of the R-290/CO2 cascade refrigeration system increase with the increase of evaporation temperature and with the decrease of condensation temperature. Moreover, the power consumption of the R-290 compressor is slightly higher than that of the R-22 compressor and the COP(h) of the R-290 cycle is higher than that of the R-22 cycle at the higher compressor inlet temperatures.

Documents disponibles

Format PDF

Pages : 57-60

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : [In Chinese. / En chinois.]
  • Identifiant de la fiche : 2008-1202
  • Langues : Chinois
  • Source : Journal of Refrigeration - vol. 28 - n. 118
  • Date d'édition : 12/2007

Liens


Voir d'autres articles du même numéro (5)
Voir la source