A3 Refrigerant R290 leak and ignition testing in whole room scale.
Fuites du frigorigène R290 de classe A3 et essais d’ignition à l’échelle d’une salle entière.
Numéro : 1040
Auteurs : WANG X.
Résumé
R290 (propane) is a class A3 refrigerant having extremely low Global Warming Potential (GWP). Its application is currently limited to small charged self-contained air-conditioning and refrigeration products in most of the world due to its flammability and safety implications. Relevant product safety standards (IEC/UL-60335-2-40 and IEC/UL-60335-2-89) are looking into increase A3 refrigerant charge limits.
To properly address R290 charge quantities in safety standards, the Air-Conditioning, Heating, and Refrigeration Technology Institute undertook R290 leak and ignition tests under whole room conditions. This paper summarizes R290 test results at current and proposed allowable charge levels for air-conditioning and refrigeration products. The test demonstrated that raising the charge limit should be carefully considered especially for floor or near floor mounted products. Any potential ignition sources should be avoided underneath installed units and near the projected area at floor level. Air circulation had a positive effect in reducing the likelihood of an ignition event.
Documents disponibles
Format PDF
Pages : 6p.
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : A3 Refrigerant R290 leak and ignition testing in whole room scale.
- Identifiant de la fiche : 30027905
- Langues : Anglais
- Sujet : Alternatives aux HFC
- Source : 14th IIR-Gustav Lorentzen Conference on Natural Refrigerants(GL2020). Proceedings. Kyoto, Japon, December 7-9th 2020.
- Date d'édition : 07/12/2020
- DOI : http://dx.doi.org/10.18462/iir.gl.2020.1040
- Disponible à la bibliothèque de l'IIF
Liens
Voir d'autres communications du même compte rendu (120)
Voir le compte rendu de la conférence
Indexation
-
Thèmes :
Hydrocarbures;
Confinement, réduction de la charge en frigorigène;
Conditionnement d'air pour le confort;
Supermarchés, meubles de vente;
Circulation du fluide : tuyauterie, régulation, automatisme, sécurité - Mots-clés : R290; Propane; Faible GWP; Inflammabilité; Chambre d'essai; Conditionneur d'air; Meuble de vente; Charge en frigorigène; Essai
-
Ignition sources at the stage of usage for mini...
- Auteurs : TAMURA K., TAKAICHI K., TAIRA S., BABA A., ITAKURA S., MORI H., MAKINO H.
- Date : 07/12/2020
- Langues : Anglais
- Source : 14th IIR-Gustav Lorentzen Conference on Natural Refrigerants(GL2020). Proceedings. Kyoto, Japon, December 7-9th 2020.
- Formats : PDF
Voir la fiche
-
A3 refrigerant R290 leak and ignition testing f...
- Auteurs : WANG X.
- Date : 26/08/2020
- Langues : Anglais
- Source : 6th IIR International Conference on Sustainability and the Cold Chain. Proceedings: Nantes, France, August 26-28 2020
- Formats : Vidéo, PDF
Voir la fiche
-
Theoretical analysis for charge reduction in a ...
- Auteurs : BAMIGBETAN O., EIKEVIK T. M., NEKSÅ P., et al.
- Date : 18/06/2018
- Langues : Anglais
- Source : 13th IIR Gustav Lorentzen Conference on Natural Refrigerants (GL2018). Proceedings. Valencia, Spain, June 18-20th 2018.
- Formats : PDF
Voir la fiche
-
Study on risk assessment of air conditioner usi...
- Auteurs : BABA A., TAKAICHI K., TAIRA S., et al.
- Date : 24/08/2019
- Langues : Anglais
- Source : Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
- Formats : PDF
Voir la fiche
-
Water to water heat pump minimum charge of prop...
- Auteurs : ANDERSSON K., GRANRYD E., PALM B.
- Date : 18/06/2018
- Langues : Anglais
- Source : 13th IIR Gustav Lorentzen Conference on Natural Refrigerants (GL2018). Proceedings. Valencia, Spain, June 18-20th 2018.
- Formats : PDF
Voir la fiche