GEL DES BATTERIES : MAINTENIR L'ECOULEMENT DES FLUIDES.

COIL FREEZING: KEEP THE FLUIDS FLOWING.

Auteurs : CLARK T. J.

Type d'article : Article

Résumé

LE PROBLEME ETUDIE EST CELUI DES BATTERIES DE CHAUFFAGE ALIMENTEES EN VAPEUR QUI SE COMPOSENT DE TUBES MULTIPLES EN PARALLELE. SI L'ALIMENTATION EST REALISEE A PARTIR D'UN COLLECTEUR SUPERIEUR, LA CONDENSATION DANS N'IMPORTE QUEL TUBE SUBISSANT DES CONDITIONS DIFFERENTES DE TRANSFERT DE CHALEUR, PAR EXEMPLE UNE MAUVAISE REPARTITION DE L'AIR SUR LA BATTERIE, SE PRODUIRA A UNE VITESSE DIFFERENTE, CAUSANT AINSI UNE PRESSION INEGALE AUX SORTIES DES TUBES, ET, DE CE FAIT, UNE TENDANCE A LA REMONTEE DU CONDENSATDANS UNE PARTIE DU BAS DE LA BATTERIE. ON ILLUSTRE QUELQUES METHODES D'ALIMENTATION QUI PERMETTENT D'EVITER CELA. UNE MAUVAISE INSTALLATION PEUT ENTRAINER DES EFFETS DE GRAVITE VARIABLE, ET UNE PURGE NON SATISFAISANTE PEUT ETRE A L'ORIGINE DE L'ACCUMULATION DE NON-CONDENSABLES. UN MAUVAIS REGLAGE DES POINTS D'OUVERTURE ET DE FERMETURE DES APPAREILS PEUT ENTRAINER UNE CONDENSATION A UNE PRESSION INFERIEURE A CELLE NSAT DANS LA BATTERIE. UN DIMENSIONNEMENT INSUFFISANT DU PIEGE DE VAPEUR PEUT EGALEMENT ETRE EN CAUSE. D.W.H.

Détails

  • Titre original : COIL FREEZING: KEEP THE FLUIDS FLOWING.
  • Identifiant de la fiche : 1991-2135
  • Langues : Anglais
  • Source : Heat. Pip. Air Cond. - vol. 62 - n. 12
  • Date d'édition : 12/1990
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres articles du même numéro (3)
Voir la source