IMPACT DE L'ACCUMULATION THERMIQUE SUR LA PERFORMANCE D'UN SYSTEME DE POMPE A CHALEUR A BOUCLE FERMEE.

IMPACT OF THERMAL STORAGE ON CLOSED-LOOP HEAT PUMP SYSTEM PERFORMANCE.

Résumé

ON A EFFECTUE LA SIMULATION D'UN IMMEUBLE UTILISANT UN SYSTEME DE CHAUFFAGE, VENTILATION ET CONDITIONNEMENT D'AIR A POMPE A CHALEUR ET A BOUCLE FERMEE, AVEC DIFFERENTES QUANTITES D'ACCUMULATION THERMIQUE, AVEC OU SANS ISOLATION DU RESERVOIR, AVEC DIVERSES CHARGES INTERNES ET PLUSIEURS LOCALISATIONS GEOGRAPHIQUES. L'EFFET DE L'ACCUMULATION D'EAU A ETE PLUS IMPORTANT POUR DES LOCALISATIONS PLUS TEMPEREES. LES AUGMENTATIONS DES CHARGES INTERNES ONT ACCRU LES CHARGES DES COMPRESSEURS ET CELLES DES TOURS DE REFROIDISSEMENT MAIS ONT DIMINUE LES BESOINS SUPPLEMENTAIRES DE FUEL ; ELLES ONT AUGMENTE LES CHARGES TOTALES DE CHAUFFAGE, VENTILATION ET CONDITIONNEMENT D'AIR DES CLIMATS CHAUDS. UNE REDUCTION DE LA LARGEUR DE LA PLAGE DE TEMPERATURES DE LA BOUCLE D'EAU DE 35-13 DEG C A 27-21 DEG C A DIMINUE L'APPORT EN ENERGIE AUX COMPRESSEURS DE 6 %, MAIS A AUGMENTE LES BESOINS SUPPLEMENTAIRES EN FUEL. L'ADDITION D'UNE LES ZONES FROIDES MAIS N'A PAS SEMBLE RENTABLE POUR LES IMMEUBLES SITUES SOUS DES CLIMATS CHAUDS.

Détails

  • Titre original : IMPACT OF THERMAL STORAGE ON CLOSED-LOOP HEAT PUMP SYSTEM PERFORMANCE.
  • Identifiant de la fiche : 1991-0835
  • Langues : Anglais
  • Date d'édition : 1989
  • Source : Source : ASHRAE Trans.
    vol. 95; n. 2; 357-365; 13 fig.; 6 tabl.; 10 ref.
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.