Impact du modèle de bâtiment virtuel et de l'installation d’un thermostat sur les performances et la dynamique des équipements à vitesse variable lors des tests basés sur la charge.
Impact of virtual building model and thermostat installation on performance and dynamics of variable-speed equipment during load-based tests.
Numéro : pap. 2713
Auteurs : CHENG L., PATIL A, DHILLON P., et al.
Résumé
To better characterize the performance of variable-speed DX (Direct Expansion) equipment in a laboratory environment, a load-based psychrometric chamber testing methodology has been developed as an alternative to existing steady-state testing approaches. The methodology allows equipment to respond dynamically to a virtual building model using its integrated controls. To mimic an actual building, a virtual building model incorporates sensible and latent loads along with simple lumped capacitance building dynamics that interact with the variablespeed equipment. The rated capacity of the test equipment is used along with a specified sizing factor and target sensible heat ratio (SHR) to specify the building sensible and latent load models.
Two companion papers (Patil el al. (2018) and Dhillon et al. (2018)) present the overall methodology and results for different variable-speed heat pumps using default building parameters. This paper studies the impact of the virtual building sizing factor on overall performance and dynamic behavior of the equipment for load-based testing. It is shown that equipment seasonal performance can increase significantly with increasing sizing factor and therefore it is important to specify representative values. In addition, performance increases with decreasing building sensible heat ratio (SHR). In addition, the impact of the thermostat location on equipment dynamics and performance ratings is considered. The seasonal performances and repeatability of load-based tests are sensitive to the choice of thermostat location. Therefore, it is important to define a strategy for locating the thermostat in a manner that will lead to reproducible results across different laboratory testing facilities.
Documents disponibles
Format PDF
Pages : 10
Disponible
Prix public
20 €
Prix membre*
15 €
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Impact of virtual building model and thermostat installation on performance and dynamics of variable-speed equipment during load-based tests.
- Identifiant de la fiche : 30024722
- Langues : Anglais
- Source : 2018 Purdue Conferences. 17th International Refrigeration and Air-Conditioning Conference at Purdue.
- Date d'édition : 09/07/2018
Liens
Voir d'autres communications du même compte rendu (252)
Voir le compte rendu de la conférence
Indexation
-
Energy efficiency in a ground source heat pump ...
- Auteurs : DEL COL D., BENASSI G., MANTOVAN M., et al.
- Date : 16/07/2012
- Langues : Anglais
- Source : 2012 Purdue Conferences. 14th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche
-
Development of a system identification model fo...
- Auteurs : HAN D. W., CHANG Y. S., KIM S. Y., et al.
- Date : 16/07/2012
- Langues : Anglais
- Source : 2012 Purdue Conferences. 14th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche
-
Optimizing energy consumption of a water-loop v...
- Auteurs : YUAN S., GRABON M.
- Date : 04/2011
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 31 - n. 5
Voir la fiche
-
Capacity control in ground source heat pump sys...
- Auteurs : MADANI H., CLAESSON J., LUNDQVIST P.
- Date : 09/2011
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 34 - n. 6
- Formats : PDF
Voir la fiche
-
Modelling of an air-to-water heat pump, equippe...
- Auteurs : DARDENNE L., FRACCARI E., MAGGIONI A., et al.
- Date : 02/09/2013
- Langues : Anglais
- Source : Compressors 2013: 8th International Conference on Compressors and Coolants.
- Formats : PDF
Voir la fiche