INFLUENCE D'UN CHAMP ELECTRIQUE SUR LE TRANSFERT DE CHALEUR PAR EBULLITION DE R11.

THE EFFECT OF AN ELECTRIC FIELD ON BOILING HEAT TRANSFER OF R11.

Auteurs : OGATA J.

Résumé

LA SECTION D'ESSAI CONSISTAIT EN UNE PLAQUE DE CUIVRE HORIZONTALE ET EN PLUSIEURS RANGEES DE FILS D'ACIER DE 0,8 MM DE DIAMETRE. LE CHAMP DE COURANT CONTINU NEGATIF A ETE APPLIQUE ENTRE UNE PLAQUE DE CUIVRE ET DES FILS D'ELECTRODES. DEUX TYPES DE SURFACES DE TRANSFERT DE CHALEUR ONT ETE CHOISIS : UNE SURFACE POLIE ET UNE SURFACE POREUSE. LES CONDITIONS EXPERIMENTALES ETAIENT UNE TEMPERATURE DE SATURATION D'ENVIRON 298 K (25 DEG C), UN FLUX THERMIQUE DE 2.400 A 13.400 W/M2, UNE TENSION APPLIQUEE DE 0 A 26 KILOVOLTS. DANS LA SURFACE POLIE, LES NOMBRES DE BULLES D'EBULLITION DIMINUAIENT AVEC UN CHAMP ELECTRIQUE, MAIS LE COEFFICIENT DE TRANSFERT DE CHALEUR PAR EBULLITION ETAIT D'ENVIRON 3 A 6 FOIS CELUI DU COEFFICIENT SANS CHAMP ELECTRIQUE. DANS LA SURFACE POREUSE UN CHAMP ELECTRIQUE NE RENFORCAIT PAS LE TRANSFERT DE CHALEUR.

Détails

  • Titre original : THE EFFECT OF AN ELECTRIC FIELD ON BOILING HEAT TRANSFER OF R11.
  • Identifiant de la fiche : 1988-1364
  • Langues : Anglais
  • Date d'édition : 01/09/1986
  • Source : Source : Proc. int. Symp. Heat Mass Transf. Refrig. Cryog., Dubr.
    140-151; 14 fig.; 1 tabl.; 13 ref.