L'ECOULEMENT D'AIR AMBIANT PAR GRAVITE PERMET D'EVITER LE SOULEVEMENT DU AU GEL SOUS LES INSTALLATIONS DE CONGELATION.

AMBIENT GRAVITY AIR FLOW PREVENTS FREEZER FLOOR HEAVING.

Auteurs : POWERS G. L.

Résumé

UNE ISOLATION SUPPLEMENTAIRE N'A PAS PERMIS DE RESOUDRE LE PROBLEME. POUR EVITER LE SOULEVEMENT DU AU GEL IL FAUT UN APPOINT DE CHALEUR. ON A UTILISE DIVERSES METHODES, TELLES QUE LE CHAUFFAGE ELECTRIQUE, DES RESEAUX DE TUYAUTERIES ET DIVERS TYPES DE LIQUIDES CHAUFFES, MIS EN CIRCULATION PAR POMPES. DEUX TYPES DE VENTILATION EN SOUS-SOL ONT ETE APPLIQUES, DONT L'UN UTILISANT DES VENTILATEURS. CE RAPPORT EXAMINE UN SYSTEME D'AIR S'ECOULANT PAR GRAVITE POUR LE CHAUFFAGE SOUS LES DALLES. LES POINTS MARQUANTS SONT L'IMPORTANCE DE LA COMPACITE DE LA SOUS-COUCHE, POUR EVITER L'ACCUMULATION D'EAU ET AINSI LE DEVELOPPEMENT DE LENTILLES DE GLACE, QUI EST LA PRINCIPALE FORCE DE SOULEVEMENT. L'ENERGIE AMBIANTE DEVIENT LA SOURCE DE CHALEUR PREFERABLE EN RAISON DE LA HAUSSE DU COUT DE L'ENERGIE.

Détails

  • Titre original : AMBIENT GRAVITY AIR FLOW PREVENTS FREEZER FLOOR HEAVING.
  • Identifiant de la fiche : 1984-1130
  • Langues : Anglais
  • Date d'édition : 1981
  • Source : Source : ASHRAE Trans.
    vol. 87; n. 2; 1107-1116; 6 fig.