AMBIENT GRAVITY AIR FLOW PREVENTS FREEZER FLOOR HEAVING.
Author(s) : POWERS G. L.
Summary
ADDITIONAL INSULATION DID NOT SOLVE THE PROBLEM. IN ORDER TO CONTROL THE HEAVING, ADDITIONAL HEAT MUST BE ADDED. VARIOUS METHODS WERE USED SUCH AS ELECTRICAL HEATING, GRID PIPING, HEATERS AND PUMPS CIRCULATING VARIOUS KINDS OF LIQUIDS. TWO TYPES OF UNDERFLOOR VENTILATION WERE USED ; ONE USING BLOWER FANS. THIS PAPER DISCUSSES A GRAVITY AIR SYSTEM FOR UNDER SLAB HEATING. THE SALIENT POINTS ARE THE IMPORTANCE OF SUBGRADE COMPACTION, TO ELIMINATE MOISTURE ACCUMULATION, THUS PREVENTING ICE LENS GROWTH, WHICH IS THE MAIN HEAVING FORCE. AMBIENT ENERGY BECOMES THE PREFERABLE HEAT SOURCE AS UTILITY RATES SPIRAL.
Details
- Original title: AMBIENT GRAVITY AIR FLOW PREVENTS FREEZER FLOOR HEAVING.
- Record ID : 1984-1130
- Languages: English
- Publication date: 1981
- Source: Source: ASHRAE Trans.
vol. 87; n. 2; 1107-1116; 6 fig. - Document available for consultation in the library of the IIR headquarters only.
Indexing
- Themes: Freezing installations
- Keywords: Civil engineering; Antifreeze protection; Ground; Ground freezing; Accident
-
A CASE HISTORY OF A FROST HEAVED REFRIGERATED F...
- Author(s) : BALLOU D. F.
- Date : 1981
- Languages : English
View record
-
BASIC CONCEPTS OF FROST HEAVING.
- Author(s) : REIN R. G. Jr, BURROUS C. M.
- Date : 1981
- Languages : English
View record
-
CIRCULATING LIQUID IN PIPE GRID SYSTEM FOR FLOO...
- Author(s) : WEBBER J. F.
- Date : 1981
- Languages : English
View record
-
USE OF COMPARATIVE COEFFICIENTS OF FROST LAYER ...
- Author(s) : KALINOWSKI E., BUCEWICZ A.
- Date : 1987/08/24
- Languages : English
- Source: Development in refrigeration, refrigeration for development. Proceedings of the XVIIth international Congress of Refrigeration.
- Formats : PDF
View record
-
OPTIMUM SOLUTIONS FOR COLD-STORAGE FLOORING AND...
- Author(s) : OHEIM H.
- Date : 1990/09/24
- Languages : English
- Formats : PDF
View record