Recommandé par l'IIF / Document IIF

Mauvaise distribution du frigorigène dans les évaporateurs d'échangeurs de chaleur à plaques Partie B: Analyse de l'influence de la mauvaise distribution sur les performances de l'évaporateur.

Refrigerant maldistribution in brazed plate heat exchanger evaporators. Part B: Analysis of the influence of maldistribution on the evaporator performance.

Auteurs : NAVARRO-PERIS E., ALVAREZ-PINEIRO L., SCHNABEL L., CORBERÁN J. M.

Type d'article : Article de la RIF

Résumé

The maldistribution of the refrigerant mass flowrate among the different channels of a brazed plate heat exchanger evaporator with distributor, has been studied with a thermographic camera working under different conditions of inlet vapor quality, superheat, and water temperature drop. Part A of this work includes the description of the experimental campaign and a full discussion of the obtained results. This paper (part B) presents, first an evaluation of the penalty caused by the refrigerant maldistribution on the evaporator performance, and the effect of the operation conditions on that penalty; second, a data reduction methodology, which allows the quantification of the maldistribution based on a series of simple assumptions and the flow conservation equations. Finally, given that it has been found that the water temperature drop across the evaporator has a strong influence on the performance penalty due to refrigerant maldistribution, the water temperature evolution is analyzed in detailed and the reasons for its great influence are explained and commented. On this regard, it is concluded that the penalty of the maldistribution on the evaporation performance strongly depends on the availability of the secondary fluid in the channels where most of the refrigerant liquid is concentrated. The described data reduction methodology, based on the analysis of the thermographies and the measured evaporator performance, is suitable to give an estimate of the maldistribution which seems reasonable and consistent with the observed data.

Documents disponibles

Format PDF

Pages : 312-321

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Refrigerant maldistribution in brazed plate heat exchanger evaporators. Part B: Analysis of the influence of maldistribution on the evaporator performance.
  • Identifiant de la fiche : 30029138
  • Langues : Anglais
  • Sujet : Technologie
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 131
  • Date d'édition : 11/2021
  • DOI : http://dx.doi.org/10.1016/j.ijrefrig.2021.04.003
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres articles du même numéro (95)
Voir la source