Document IIF
Mauvaise distribution du frigorigène dans les évaporateurs d'échangeurs de chaleur à plaques.
Refrigerant maldistribution in brazed plate heat exchanger evaporators. Part A: Testing campaign and experimental results.
Auteurs : NAVARRO-PERIS E., ALVAREZ-PINEIRO L., ALBALADEJO P., SCHNABEL L., CORBERÁN J. M.
Type d'article : Article de la RIF
Résumé
The refrigerant distribution in a brazed plate heat exchanger evaporator with distributor has been studied with a thermographic camera working under different conditions of inlet vapor quality, superheat, and water temperature drop. The thermographies have shown a clear uneven thermal distribution except when superheat is null. In most of the cases, they show that a great part of the liquid accumulates at the end channels of the evaporator. The degradation of the evaporator performance is higher when the water temperature drop has a similar or higher value than the superheat. On the other hand, when the superheat is significantly higher than the water temperature drop, the evaporator performance is very similar to situations in which there is an even distribution of the refrigerant. The registered evaporation temperatures are much lower for the case of 13 K of water temperature drop, highlighting the importance of the influence of this parameter on the evaporator performance. This research is described in two parts, Part A (present paper) including the description of the experimental campaign, the obtained experimental results and the results discussion and Part B including an analysis of the degradation of the evaporation temperature due to the refrigerant maldistribution as well as a deeper analysis of the registered temperatures and of the causes for the great degradation observed when the water temperature drop is increased.
Documents disponibles
Format PDF
Pages : 119-128
Disponible
Gratuit
Détails
- Titre original : Refrigerant maldistribution in brazed plate heat exchanger evaporators. Part A: Testing campaign and experimental results.
- Identifiant de la fiche : 30029120
- Langues : Anglais
- Sujet : Technologie
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 131
- Date d'édition : 11/2021
- DOI : http://dx.doi.org/10.1016/j.ijrefrig.2021.04.002
- Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.
Liens
- Voir les traductions : Refrigerant maldistribution in brazed plate heat exchanger evaporators. Part B: Analysis of the influence of maldistribution on the evaporator performance.
Voir d'autres articles du même numéro (95)
Voir la source
-
Investigation on performance and refrigerant di...
- Auteurs : WEI W., XU G., JI J.
- Date : 03/2024
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 159
- Formats : PDF
Voir la fiche
-
A new method for estimating the refrigerant dis...
- Auteurs : ZHANG S., LI Y., XU Y., YANG J., WANG Q.
- Date : 06/2021
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 126
- Formats : PDF
Voir la fiche
-
PRODUCT TREATMENT IN PLATE HEAT EXCHANGER.
- Auteurs : JENSEN B.
- Date : 1988
- Langues : Danois
- Source : North Eur. Dairy J. - vol. 54 - n. 6
Voir la fiche
-
Fluid temperature and velocity effect on fouling.
- Auteurs : KUKULKA D. J., DEVGUN M.
- Date : 11/2007
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 27 - n. 16
Voir la fiche
-
Quantification of flow distribution and heat ca...
- Auteurs : LI H., WANG L., JIANG H., LIU H., GAO Q., HUANG L.
- Date : 02/2023
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 146
- Formats : PDF
Voir la fiche