Document IIF
Mesures sur site d’un système frigorifique de supermarché à basse température au R404A, converti au R449A.
Field measurements of a R404A low-temperature supermarket refrigeration system retrofitted with R449A.
Numéro : pap. 61
Auteurs : MAKHNATCH P., MOTA BABILONI A., KHODABANDEH R., et al.
Résumé
Current international regulations set incentives to replace refrigerants with high global warming potential (GWP) values using environmentally friendly alternatives. This study presents the field measurements of an indirect commercial refrigeration system retrofitted with R449A, an alternative to R404A with a GWP value of 1282 (67% lower than that of R404A). The system has been operated at low evaporation temperature conditions(secondary refrigerant temperatures from -34 to -25 ? ). The results indicate that the cooling capacity of the retrofitted system was 1.3% lower than that of the reference R404A system on average, while the COP values are higher when using R449A (8.1% increase on average). The compressor discharge temperature increase is approximately 18.5 K. As a conclusion, R449A can be used as a replacement to R404A in indirect low-temperature supermarket refrigeration systems given that implications of its higher compressor discharge temperature, lower mass flow and difference in transport properties are taken into consideration.
Documents disponibles
Format PDF
Pages : 7
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Field measurements of a R404A low-temperature supermarket refrigeration system retrofitted with R449A.
- Identifiant de la fiche : 30023415
- Langues : Anglais
- Source : 5th IIR International Conference on Sustainability and the Cold Chain. Proceedings: Beijing, Chine, 6-8 avril 2018
- Date d'édition : 06/04/2018
- DOI : http://dx.doi.org/10.18462/iir.iccc.2018.0061
Liens
Voir d'autres communications du même compte rendu (72)
Voir le compte rendu de la conférence
Indexation
-
Thèmes :
HFC;
Supermarchés, meubles de vente;
Mélanges - Mots-clés : Basse température; Remplacement immediat; R449A; R404A; Supermarché; Performance; Experimentation; Conversion; Frigorigène
-
Replacement of R-404A refrigerant in supermarkets.
- Auteurs : CALMELS O., MICHINEAU T., SUQUET T.
- Date : 24/08/2019
- Langues : Anglais
- Source : Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
- Formats : PDF
Voir la fiche
-
Retrofit of lower GWP alternative R449A into an...
- Auteurs : MAKHNATCH P., MOTA BABILONI A., ROGSTAM J., et al.
- Date : 04/2017
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 76
- Formats : PDF
Voir la fiche
-
Semi-empirical analysis of HFC supermarket refr...
- Auteurs : MOTA BABILONI A., GIMÉNEZ-PRADES P., MAKHNATCH P., ROGSTAM J., FERNANDEZ MORENO A., NAVARRO-ESBRÍ J.
- Date : 05/2022
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 137
- Formats : PDF
Voir la fiche
-
R-407H as drop-in of R-404A. Experimental analy...
- Auteurs : LLOPIS R., SÁNCHEZ D., CABELLO R., et al.
- Date : 08/2017
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 80
- Formats : PDF
Voir la fiche
-
Development of low global warming potential ref...
- Auteurs : ABDELAZIZ O., FRICKE B., VINEYARD E.
- Date : 16/07/2012
- Langues : Anglais
- Source : 2012 Purdue Conferences. 14th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche