Modèle simplifié de la dispersion des agents contaminants dans des pièces climatisées grâce à un système de ventilation par déplacement et un plafond froid.

Simplified model of contaminant dispersion in rooms conditioned by chilled-ceiling displacement ventilation system.

Auteurs : KANAAN M., GHADDAR N., GHALI K.

Type d'article : Article

Résumé

The aim of the paper is to develop and experimentally validate a simplified model to predict carbon dioxide transport and distribution in rooms conditioned by chilled-ceiling displacement ventilation system for known supply thermal and flow conditions and chilled-ceiling temperature. The transport model of carbon dioxide considers upward convective flow by the rising thermal wall and source plumes, the CO2 lateral diffusion into plume-adjacent air layers, and vertical CO2 diffusion in air inside and outside the plumes. Experiments were performed for different supply air CO2 concentrations, supply air flow rates, and strengths of heat sources. Experimental measurements of the vertical profile of air temperature, and carbon dioxide concentration compared well with values calculated by the model. The indoor air quality is assessed based on levels of carbon dioxide concentration in the radiant-cooled space. The model can be put to practical use in finding the maximum acceptable fraction of return air to be mixed with the supply while the air quality in the breathing zone remains acceptable.

Détails

  • Titre original : Simplified model of contaminant dispersion in rooms conditioned by chilled-ceiling displacement ventilation system.
  • Identifiant de la fiche : 2010-1983
  • Langues : Anglais
  • Source : HVAC&R Research - vol. 16 - n. 6
  • Date d'édition : 11/2010
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir la source