Simplified model of contaminant dispersion in rooms conditioned by chilled-ceiling displacement ventilation system.
Author(s) : KANAAN M., GHADDAR N., GHALI K.
Type of article: Article
Summary
The aim of the paper is to develop and experimentally validate a simplified model to predict carbon dioxide transport and distribution in rooms conditioned by chilled-ceiling displacement ventilation system for known supply thermal and flow conditions and chilled-ceiling temperature. The transport model of carbon dioxide considers upward convective flow by the rising thermal wall and source plumes, the CO2 lateral diffusion into plume-adjacent air layers, and vertical CO2 diffusion in air inside and outside the plumes. Experiments were performed for different supply air CO2 concentrations, supply air flow rates, and strengths of heat sources. Experimental measurements of the vertical profile of air temperature, and carbon dioxide concentration compared well with values calculated by the model. The indoor air quality is assessed based on levels of carbon dioxide concentration in the radiant-cooled space. The model can be put to practical use in finding the maximum acceptable fraction of return air to be mixed with the supply while the air quality in the breathing zone remains acceptable.
Details
- Original title: Simplified model of contaminant dispersion in rooms conditioned by chilled-ceiling displacement ventilation system.
- Record ID : 2010-1983
- Languages: English
- Source: HVAC&R Research - vol. 16 - n. 6
- Publication date: 2010/11
- Document available for consultation in the library of the IIR headquarters only.
Links
- External links:
See the source
Indexing
-
Chilled ceilings: chilling lessons.
- Author(s) : BUNN R.
- Date : 1995/05
- Languages : English
- Source: J. chart. Inst. Build. Serv. - vol. 17 - n. 5
View record
-
Low-cost dedicated outdoor-air systems.
- Author(s) : WEST M.
- Date : 2010/07
- Languages : English
- Source: HPAC Engineering - vol. 82 - n. 7
View record
-
Ventilazione naturale.
- Author(s) : LENZUNI P., DEL GAUDIO M.
- Date : 2005/05
- Languages : Italian
- Source: Cond. Aria - n. 5
View record
-
Measuring IAQ parameters.
- Author(s) : BEARG D. W.
- Date : 2008/08
- Languages : English
- Source: HPAC Engineering - vol. 80 - n. 8
View record
-
CO2 levels in auditoriums.
- Author(s) : CHAUHAN M. M., BHOLANDA J. V., MANGLANI A. K.
- Date : 2005/04
- Languages : English
- Source: Air Conditioning and Refrigeration Journal - vol. 8 - n. 2
- Formats : PDF
View record