Document IIF
Modèle unidimensionnel pour la détermination du ratio d'entraînement d'un éjecteur.
A one dimensional model for the determination of an ejector entrainment ratio.
Auteurs : GARCÍA del VALLE J., SAIZ JABARDO J. M., CASTRO RUIZ F., et al.
Type d'article : Article, Article de la RIF
Résumé
The proposed model is a new approach for the evaluation of the entrainment ratio of double choked ejectors, based on a perturbation procedure of linearized and axisymmetric supersonic flow. The model is developed in three regions: (i) the primary flow nozzle, (ii) the secondary flow channel, and (iii) the region of interaction between the supersonic nozzle jet and the secondary flow. Primary and secondary flows are assumed isentropic. A simultaneous numerical solution of the governing equations of the three regions is obtained by dividing the external supersonic jet flow in small volumes, where the external pressure, corresponding to the secondary flow pressure, is assumed constant in each volume. The model has been evaluated against experimental results obtained elsewhere, especially data from the Huang et al. (1999) investigation. The absolute average deviation of model entrainment ratio with respect to experimental data is of the order of 7%
Documents disponibles
Format PDF
Pages : 772-784
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : A one dimensional model for the determination of an ejector entrainment ratio.
- Identifiant de la fiche : 30003984
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 35 - n. 4
- Date d'édition : 06/2012
Liens
Voir d'autres articles du même numéro (45)
Voir la source
Indexation
-
The effect of operating conditions on the perfo...
- Auteurs : AIDOUN Z., OUZZANE M.
- Date : 12/2004
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 27 - n. 8
- Formats : PDF
Voir la fiche
-
Modelling and optimization of two-phase ejector...
- Auteurs : CIZUNGU K., GROLL M., LING Z. G.
- Date : 09/2005
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 25 - n. 13
Voir la fiche
-
Modelling of an ejector refrigerating system op...
- Auteurs : BOUMARAF L., LALLEMAND A.
- Date : 02/2009
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 29 - n. 2-3
Voir la fiche
-
A theoretical study on a novel bi-ejector refri...
- Auteurs : ZHANG B., SHEN S.
- Date : 04/2006
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 26 - n. 5-6
Voir la fiche
-
Optimization of a hybrid ejector air conditioni...
- Auteurs : WANG H., CAI W., WANG Y.
- Date : 05/02/2017
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 112
Voir la fiche