Modélisation des cycles à adsorption à pompes à chaleur : processus d'onde thermique avec équilibre local.

Adsorption heat pump modelling: the thermal wave process with local equilibrium.

Auteurs : SWARD B. K., LEVAN M. D., MEUNIER F.

Type d'article : Article

Résumé

This paper describes a model for a thermal-wave adsorption heat pump cycle. Local equilibrium is assumed, providing the asymptotic best-case performance. The model is utilized to examine the performance of adsorption refrigeration cycles powered by low temperature waste heat sources of 373-393 K. The impact of varying system temperatures, bed cycling frequency, valve positioning, and sectioning of the bed are examined. Cycle COPs were greater than 1.2 for the base case of a 393 K heat source, 303 K condenser temperature, and 278 K evaporator temperature for a cycle utilizing a water/NaX zeolite adsorbate/adsorbent pair.

Détails

  • Titre original : Adsorption heat pump modelling: the thermal wave process with local equilibrium.
  • Identifiant de la fiche : 2001-0776
  • Langues : Anglais
  • Source : Applied Thermal Engineering - vol. 20 - n. 8
  • Date d'édition : 06/2000

Liens


Voir d'autres articles du même numéro (3)