Document IIF
Nouvelle méthode d'optimisation structurelle pour les distributeurs de conditionneurs d'air fonctionnant au R290 équipés de tubes en cuivre de petit diamètre.
A new structural optimization method for distributors in R290 air conditioner with small diameter copper tubes.
Résumé
R290 (propane) is one of the most potential natural working fluids due to its zero Ozone Depletion Potential (ODP) and low Global Warming Potential (GWP). However, the apply of R290 in air conditioner is inevitably limited because of its inflammability. The air conditioner with small diameter copper tubes can reduces refrigerant charge, ensuring the safety and reliability of R290 while increasing the flow paths can enlarges the risk of uneven distribution. Employing highperformance distributors ensures a uniform flow distribution for R290 room air conditioner (RAC). In this paper, a simulation-based structural optimization method has been investigated for distributor design, in which a mass flow distribution model has been verified and used for simulation. A new
prototype based on this method is developed and experimentally tested in an air conditioner using R290 and 5mm diameter tubes, comparing with the conventional one. It is shown that the new prototype improves energy efficiency ratio as much as 2.2% under small air flow rate mode and 2.7% under large air flow rate mode. The experimental results validate the optimization effect of the
structural method for distribution design in RAC.
Documents disponibles
Format PDF
Pages : 8 p.
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : A new structural optimization method for distributors in R290 air conditioner with small diameter copper tubes.
- Identifiant de la fiche : 30019136
- Langues : Anglais
- Source : 12th IIR Gustav Lorentzen Conference on Natural Refrigerants (GL2016). Proceedings. Édimbourg, United Kingdom, August 21st-24th 2016.
- Date d'édition : 21/08/2016
- DOI : http://dx.doi.org/10.18462/iir.gl.2016.1053
Liens
- Voir les traductions : Un nuevo método de optimización estructural para distribuidores en aire acondicionado R290 con tubos de cobre de pequeño diámetro.
Voir d'autres communications du même compte rendu (140)
Voir le compte rendu de la conférence
Indexation
-
Performance simulation of an inverter operated ...
- Auteurs : UTAGE A., PHADAKE H., MALI K.
- Date : 21/08/2023
- Langues : Anglais
- Source : Proceedings of the 26th IIR International Congress of Refrigeration: Paris , France, August 21-25, 2023.
- Formats : PDF
Voir la fiche
-
Study on PMF rotary compressor for unitary air ...
- Auteurs : GAO B., GAO Q., LI H., HUANG J.
- Date : 05/2021
- Langues : Anglais
- Source : 2021 Purdue Conferences. 25th International Compressor Engineering Conference at Purdue.
- Formats : PDF
Voir la fiche
-
The first 60,000 HC-290 split air conditioners ...
- Auteurs : RAJADHYAKSHA D., WADIA B. J., COLBOURNE D.
- Date : 02/08/2014
- Langues : Anglais
- Source : 11th IIR Gustav Lorentzen Conference on Natural Refrigerants (GL2014). Proceedings. Hangzhou, China, August 31-September 2, 2014.
- Formats : PDF
Voir la fiche
-
Investigation of the practical method for enhan...
- Auteurs : TANG W., HE G., CAI D., et al.
- Date : 23/04/2017
- Langues : Anglais
- Source : 5th IIR Conference on Thermophysical Properties and Transfer Processes of Refrigerants.
- Formats : PDF
Voir la fiche
-
Development of a propane double duct room air c...
- Auteurs : RIGHETTI G., CAMPIDELLI M., BOTTARO M., et al.
- Date : 24/08/2019
- Langues : Anglais
- Source : Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
- Formats : PDF
Voir la fiche