Optimisation de la performance d'une pompe à chaleur géothermique hybride dotée d'un échangeur de chaleur géothermique à configuration parallèle et d'un dispositif d'évacuation de chaleur en mode refroidissement.

Performance optimization of a hybrid ground source heat pump with the parallel configuration of a ground heat exchanger and a supplemental heat rejecter in the cooling mode.

Auteurs : PARK H., LEE J. S., KIM W., et al.

Type d'article : Article, Article de la RIF

Résumé

A hybrid ground source heat pump (HGSHP) combining a ground flow loop and a supplemental heat rejecter loop in parallel is proposed to overcome the degradation of the ground thermal condition. The objective of this study is to optimize the performance of the HGSHP with the parallel configuration by varying the amount of refrigerant charge, the secondary fluid flow rate of the ground loop, and the secondary fluid flow rate of the supplemental loop. The coefficient of performance (COP) of the HGSHP with the parallel configuration was 21% higher than that of the conventional ground source heat pump (GSHP), and the heat rejection rate of the ground flow loop was 42% lower than that of the GSHP at the entering fluid temperature (EFT) of 40°C in the ground heat exchanger and the EFT of 28°C in the supplemental heat exchanger.

Documents disponibles

Format PDF

Pages : 1537-1546

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Performance optimization of a hybrid ground source heat pump with the parallel configuration of a ground heat exchanger and a supplemental heat rejecter in the cooling mode.
  • Identifiant de la fiche : 30004792
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 35 - n. 6
  • Date d'édition : 09/2012