Uniform distribution of the two-phase refrigerant is the key to maximizing the capacity of microchannel evaporators. The high operating pressure of CO2 refrigerant requires use of many flat multiport tubes in both the evaporator and gas cooler. The effects of refrigerant quality maldistribution are quantified and means to counter it are explored. Liquid-only feed, with flash gas bypass, is then investigated in more detail. Performance is compared for passive vapour bypass devices, demonstrating successful elimination of quality maldistribution by their use, with no significant impact on the system performance.

Documents disponibles

Format PDF

Pages : 2002-5

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Optimizing the effectiveness of R744 microchannel evaporators.
  • Identifiant de la fiche : 2003-2214
  • Langues : Anglais
  • Date d'édition : 17/09/2002
  • Source : Source : Proc. 5th IIR-Gustav Lorentzen Conf. nat. Working Fluids, Guangzhou/ C. R. Conf. Guangzhou, IIF
    2002-5; sess. 2; pap. 30; 248-254; fig.; tabl.; 15 ref.