Performance commerciale à long terme des pompes à chaleur géothermiques. 3. Températures des boucles.

Long-term commercial GSHP performance. 3. Loop temperatures.

Auteurs : KAVANAUGH S., KAVANAUGH J.

Type d'article : Article

Résumé

Ground loop temperatures have a significant impact on system performance. Systems with maximum average ground loop temperatures below 90°F (32°C) had an average ENERGY STAR rating of 92 while those with temperatures above 95°F (35°C) had an average rating of 53. This article is the third in a series that summarizes a data collection and analysis project to identify common characteristics of successful ground source heat pump (GSHP) systems.