Performance de chauffage d'un système de chauffage d'eau à pompe à chaleur au CO2.

The heating performance of a CO2 heat pump water heater.

Auteurs : BAEK C., LEE E., KANG H., et al.

Résumé

In this study, an experimental study on the heating performance of a CO2 heat pump water heater was performed with a variation of operating conditions such as refrigerant charge amount, outdoor temperature, compressor frequency, EEV opening and water mass flow rate. Based on the test results, the optimum charge amount was 1800 g. At the water mass flow rates of 75, 85, and 95 kg/h, the water heating temperatures were 62, 67, and 74°C and COPs were 2.6, 2.8, and 3.0, respectively. Besides, the water mass flow rate and compressor frequency were varied to maintain the water heating temperature above 609: with the decrease of outdoor temperature. Thus, the compressor frequency increased beyond 60 Hz and the water mass flow rate was 45 kg/h at the outdoor temperature of -13°C, 65 kg/h at -8°C, 75 kg/h at -3°C, and 85 kg/h at 2,7°C. As the outdoor temperature decreased, the COP decreased by 2.5-39.8%.

Documents disponibles

Format PDF

Pages : pp. 311-316

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : The heating performance of a CO2 heat pump water heater.
  • Identifiant de la fiche : 2009-2515
  • Langues : Anglais
  • Source : ACRA-2009. The proceedings of the 4th Asian conference on refrigeration and air conditioning: May 20-22, 2009, Taipei, R.O.C.
  • Date d'édition : 20/05/2009

Liens


Voir d'autres communications du même compte rendu (102)
Voir le compte rendu de la conférence