Performance des diffuseurs à débit d'air variable utilisant des ventilateurs : dispositif expérimental et méthodologie.

Performance of VAV fan-powered terminal units: experimental setup and methodology.

Auteurs : FURR J. C., O'NEAL D. L., DAVIS M. A., et al.

Résumé

This paper is the first of three papers on the development of experimental performance models of variable air volume fan powered terminal units (see also this Bulletin, references 2009-1275 and 1276. Tests were conducted on both parallel and series fan powered terminal units. Data from these tests were used to develop empirical models of airflow, power, and leakage of both parallel and series fan power terminal units. These models are suitable for use in annual energy use models of variable air volume systems in commercial buildings. This paper provides a description of the experimental apparatus, the terminal units, and measurements for airflow and power. Both 8 in. (203 mm) and 12 in. (304 mm) primary air inlet terminal units from three manufacturers were evaluated.

Détails

  • Titre original : Performance of VAV fan-powered terminal units: experimental setup and methodology.
  • Identifiant de la fiche : 2009-1274
  • Langues : Anglais
  • Source : ASHRAE Transactions. 2008 Winter Meeting, New York City, NY. Volume 114, part 1 + CD-ROM.
  • Date d'édition : 19/01/2008