PERFORMANCE DES ECHANGEURS DE CHALEUR AIR-AIR POUR LOCAUX RESIDENTIELS AU COURS DU FONCTIONNEMENT AVEC GIVRAGE ET DEGIVRAGES PERIODIQUES.

PERFORMANCE OF RESIDENTIAL AIR-TO-AIR HEAT EXCHANGERS DURING OPERATION WITH FREEZING AND PERIODIC DEFROSTS.

Auteurs : FISK W. J.

Résumé

DANS UNE ETUDE DE LABORATOIRE DE LA PERFORMANCE DES ECHANGEURS DE CHALEUR AIR-AIR POUR LOCAUX RESIDENTIELS AU COURS DU FONCTIONNEMENT AVEC GIVRAGE ET DEGIVRAGES PERIODIQUES, LE GIVRAGE A ABAISSE LE RENDEMENT THERMIQUE D'UN ECHANGEUR DE CHALEUR A COURANT CROISE DE 1,5 A 13,2 %/H ET D'UN ECHANGEUR DE CHALEUR A CONTRE-COURANT A 0,6 A 2,0 %/H. LE TEMPS NECESSAIRE POUR DEGIVRER LE CENTRE DE L'ECHANGEUR DE CHALEUR ETAIT DE 6 A 26 % DU TEMPS DE FONCTIONNEMENT TOTAL. LES RESULTATS AMENENT A PENSER QUE LA RAPIDITE DES DETERIORATIONS DE LA PERFORMANCE PEUT ETRE REDUITE EN EVITANT LES PETITS PASSAGES D'ECOULEMENT D'AIR.

Détails

  • Titre original : PERFORMANCE OF RESIDENTIAL AIR-TO-AIR HEAT EXCHANGERS DURING OPERATION WITH FREEZING AND PERIODIC DEFROSTS.
  • Identifiant de la fiche : 1986-1602
  • Langues : Anglais
  • Date d'édition : 1985
  • Source : Source : ASHRAE Trans.
    vol. 91; n. 1B; 159-172; 8 fig.; 2 tabl.; 1 ref.