Document IIF

Performance des frigorigènes HC et HFC dans un évaporateur à tube aileté et son impact sur l'efficacité du système.

Performance of HC and HFC refrigerants in a finned-tube evaporator and its effect on system efficiency.

Résumé

The paper presents a comparable evaluation of isobutane (R600a), propane (R290), R134a, R22, R410A, and R32 in an optimized finned-tube evaporator, and analyzes the impact of evaporator effects on the system COP. The study relied on a detailed evaporator model derived from NIST's EVAP-COND simulation package and used the ISHED1 scheme employing a non-Darwinian Learnable Evolution Model for circuitry optimization. For a theoretical cycle analysis without accounting for evaporator effects, the COP spread for the studied refrigerants was as high as 11.7%. For cycle simulations including evaporator effects, the COP of R290 was better than that of R22 by up to 3.5%, while the remaining refrigerants performed within approximately a 2% COP band of the R22 baseline for the two condensing temperatures considered.

Documents disponibles

Format PDF

Pages : 2004-2

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Performance of HC and HFC refrigerants in a finned-tube evaporator and its effect on system efficiency.
  • Identifiant de la fiche : 2005-2453
  • Langues : Anglais
  • Source : Natural Working Fluids 2004: 6th IIR-Gustav Lorentzen Conference
  • Date d'édition : 01/08/2004

Liens


Voir d'autres communications du même compte rendu (105)
Voir le compte rendu de la conférence