PERFORMANCES COMPARATIVES DU R134A ET DU R12 DANS UN GROUPE REFROIDISSEUR D'EAU A PISTONS.

COMPARATIVE PERFORMANCES OF R134A AND R12 IN A RECIPROCATING WATER CHILLER.

Résumé

LES AUTEURS ONT CONCU ET TESTE UN GROUPE REFROIDISSEUR D'EAU EXPERIMENTAL DE 15 KILOWATTS EQUIPE D'UN COMPRESSEUR A PISTON HERMETIQUE ACCESSIBLE CHARGE AVEC DE L'HUILE MINERALE NAPHTENIQUE. ON A OBSERVE UNE BONNE CORRELATION ENTRE LES MESURES DIRECTES DE LA CONSOMMATION TOTALE D'ENERGIE DU COMPRESSEUR ET LA CAPACITE FRIGORIFIQUE DE L'EVAPORATEUR AINSI QUE LES PERFORMANCES DEDUITES A PARTIR DES MESURES SUR LE CIRCUIT DE FRIGORIGENE. ON RAPPORTE ET ON DISCUTE DES PERFORMANCES THERMODYNAMIQUES COMPARATIVES POUR LE R134A ET LE R12 POUR UNE PLAGE DE TEMPERATURES D'EAU GLYCOLEE FROIDE DE 263 A 278 K (-10 A 5 DEG C) ET POUR UNE TEMPERATURE CONSTANTE DE CONDENSATION DE 305,5 K (32,5 DEG C). APRES 500 HEURES DE FONCTIONNEMENT CONTINU, ON N'A OBSERVE AUCUN MAUVAIS FONCTIONNEMENT MECANIQUE OU BAISSE DE LA PERFORMANCE, QUI AURAIENT ETE DUS A LA NON MISCIBILITE DU R134A AVEC DE L'HUILE.

Détails

  • Titre original : COMPARATIVE PERFORMANCES OF R134A AND R12 IN A RECIPROCATING WATER CHILLER.
  • Identifiant de la fiche : 1991-1125
  • Langues : Anglais
  • Date d'édition : 17/07/1990
  • Source : Source : USNC-IIR/Proc. 1990 Refrig. Conf., Purdue Univ./ASHRAE, Purdue CFC Conf./Purdue Univ., Ray W. Herrick Lab., Sch. mech. Eng.
    354-364; 9 fig.; 2 tabl.; 4 ref.
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.