Document IIF

Performances élémentaires du système frigorifique cyclonique au CO2.

Basic performance of CO2 cyclone refrigeration system.

Résumé

The CO2 refrigeration system is unique in a way that the sublimation heat of dry-ice made at the expansion process is utilized by a newly designed cyclone separator-evaporator in the low-pressure cycle side of a cascade heat pump cycle. In the present study, the effectiveness of the cyclone separator-evaporator is examined and the basic performance of the system is evaluated by measuring temperature and pressure obtained by the cyclone separator-evaporator. The system performance is at the same time verified by adopting the exergy analysis of the system. The results of the present study show a promising outcome from the experimental system, such that avoidance of dry-ice blockage in the conventional evaporator is possible in the temperature range below -56.6˚C.

Documents disponibles

Basic Performance of CO2 Cyclone Refrigeration System

Pages : 6

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Basic performance of CO2 cyclone refrigeration system.
  • Identifiant de la fiche : 30027920
  • Langues : Anglais
  • Sujet : Technologie
  • Source : 14th IIR-Gustav Lorentzen Conference on Natural Refrigerants (GL2020). Proceedings. Kyoto, Japon, December 7-9th 2020.
  • Date d'édition : 07/12/2020
  • DOI : http://dx.doi.org/10.18462/iir.gl.2020.1199

Liens


Voir d'autres communications du même compte rendu (120)
Voir le compte rendu de la conférence