Plusieurs problèmes dans le calcul thermodynamique des refroidisseurs d'air à tubes ailetés.

[In Chinese. / En chinois.]

Auteurs : WANG L., MA J.

Type d'article : Article

Résumé

The article discusses the application of the two commonly used conclusions in the thermodynamic calculation of surface air coolers, i.e. "the same enthalpy of inlet air, the same enthalpy of outlet air" and "the mean coil surface state is on the line of the state points of the inlet and the outlet air". It verifies them according to the thermodynamic calculating formulas and points out that the mean coil surface state is approximatively existent under wet conditions. The article also discusses the shortcoming and rationality of the method of judging work conditions by mean coil surface state and it puts forward a method to judge work conditions of the fully dry, partially dry and fully wet. Analyses and demonstrates the method by a detailed calculation.

Documents disponibles

Format PDF

Pages : 43-48

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : [In Chinese. / En chinois.]
  • Identifiant de la fiche : 2008-1319
  • Langues : Chinois
  • Source : HV & AC - vol. 37 - n. 205
  • Date d'édition : 11/2007

Liens


Voir d'autres articles du même numéro (7)
Voir la source